Roof Rainwater Catchment System
Turn every square metre of roof into a water supply
Difficulty
Intermediate
Build time
2 weekends
Material cost
$600 – $2,500
Crew
2 people
Overview
A complete catchment run: roof surface, gutters, leaf screening, a first-flush diverter that dumps the dirty opening water, then storage in food-grade tanks with an overflow that protects your foundations. This is the cheapest water per litre you will ever get on a property, and it scales — add tanks in parallel as budget allows. Build the collection side properly first; treatment (W-03) is a separate stage and should never be used to compensate for a filthy roof.
Key figures
- Yield formula
- Roof ft² × rain in × 0.623 × 0.85 = gallons
- Typical tank
- 1,500 – 5,000 gal poly
- First flush
- 10 gal per 1,000 ft² of roof
- Pipe size
- 3 in downpipe, 2 in tank inlet
- Tank pad load
- 8.34 lb per gallon — 1,500 gal ≈ 12,500 lb
Read before starting
- 01A full tank is lethal if it tips. Build the pad dead level on compacted base — never on soft ground, timber blocks or a slope.
- 02Do not collect from asphalt shingle, treated timber shakes, lead flashing or copper-treated moss killer for potable use. Metal roofs only for drinking water.
- 03Cover every opening with insect mesh. Open tanks breed mosquitoes and drown wildlife.
- 04Check local law — rainwater harvesting is restricted or permit-only in some US states and Australian councils.
- 05Work off a stable ladder tied at the top when hanging gutters. Most catchment injuries are falls, not water.
Procedure
0/7 completeCalculate your yield and size the tanks
Measure roof footprint (plan area, not sloped area). Multiply ft² × annual rainfall in inches × 0.623 to get raw gallons, then multiply by 0.85 for real-world losses. Compare to demand: budget 50 gal/person/day for full off-grid living, or 15 gal/person/day in strict conservation mode. Size storage for your longest dry spell, not your average month.
Field tip · Two 1,500 gal tanks plumbed together beat one 3,000 gal tank — you can clean one while the other stays in service, and they fit through gates.
Build the tank pad
Excavate 8 in below grade, 12 in wider than the tank on all sides. Lay and compact 6 in of road base in two lifts, checking level between each. Top with 2 in of screeded sand. The pad must be level within 1/4 in across its full width — a leaning poly tank will split its seam within a season.
Hazard · Never place a tank on a timber deck, pavers or bare topsoil. A 1,500 gal tank weighs about 12,500 lb full.
Hang the gutters with correct fall
Snap a chalk line from the high end to the downpipe end with 1/16 in of fall per foot of run. Fix hangers every 24 in (every 18 in in snow country) into rafter tails, not fascia board alone. Seal joints with gutter sealant, not silicone — silicone fails on aluminium within two summers.
Field tip · Run a garden hose in the far end before you fit the downpipe. Any pooling shows up instantly and is a five-minute fix at this stage.
Fit leaf screening
Install micro-mesh guards over the full gutter run and a leaf strainer basket at each downpipe head. The goal is that nothing bigger than grit ever enters the pipework — organics in the tank are what create the sulphur smell people blame on the tank itself.
Install the first-flush diverter
Plumb a vertical 4 in PVC chamber off the downpipe before the tank tee, sized at 10 gallons per 1,000 ft² of roof. Add a floating ball seal at the top and a slow-release drip valve (1/16 in orifice) at the bottom so the chamber empties itself between storms. The first minutes of runoff carry the dust, bird droppings and pollen — that water goes to the garden, never to the tank.
Hazard · A diverter that does not drain becomes a stagnant bacteria reservoir. Test the drip valve every season.
Connect inlet, overflow and outlet
Cut the tank inlet with a hole saw and fit a screened strainer basket. Install bulkhead fittings for the outlet (150 mm above the tank floor so sediment stays behind) and the overflow (same diameter or larger than the combined inlets). Route the overflow well away from the tank pad and any foundation, and screen its outlet against rodents.
Field tip · A calmed inlet — an elbow turning the flow downward against the wall — stops incoming water stirring up the sediment layer.
Commission and test
Fill 12 in of water and check the pad for settlement before continuing. Fill fully and inspect every fitting for weeps. Run a full storm cycle and watch the first-flush chamber fill, seal and drain. Record the date on the tank in permanent marker — that becomes the start of your maintenance log.
Maintenance schedule
Fault finding
Water smells of rotten eggs
Likely causeAnaerobic decay of organics in the sediment layer
CorrectionImprove leaf screening, raise the outlet off the floor, and sludge-clean the tank. Aerate by recirculating with the pump for an hour.
Gutter overflows in heavy rain
Likely causeUndersized downpipe or blocked strainer
CorrectionClear the strainer; if it recurs, add a second downpipe. One 3 in downpipe drains roughly 1,200 ft² of roof.
Green water
Likely causeLight reaching the tank interior
CorrectionReplace translucent tanks or shade-paint them. Algae cannot grow in the dark — this is a light problem, never a chemistry problem.
Tank leaning after 6 months
Likely causePad settlement or uncompacted base
CorrectionDrain, re-level and re-compact. Do not shim with timber.