Backup Generator & Automatic Integration
The insurance policy for the fourth grey day
Difficulty
Intermediate
Build time
1 – 2 days
Material cost
$1,000 – $6,000
Crew
1 – 2 people
Overview
Every off-grid system needs a generator, and almost everyone buys the wrong one. This entry covers sizing against the inverter/charger rather than the house load, fuel strategy, the difference between a two-wire-start auto system and manual operation, safe transfer switching, and the maintenance regime that means it will actually start when it matters.
Key figures
- Sizing rule
- Match inverter/charger AC input, not house load
- Typical size
- 5 – 8 kW for a 6 kW inverter
- Run-in efficiency
- Load it to 60 – 80% for clean burn
- Fuel burn
- ~0.6 – 0.9 gal/hr at half load (petrol)
- Service interval
- 100 hrs oil, 200 hrs full
Read before starting
- 01Carbon monoxide from a generator kills silently. Never run one in a shed, garage, or within 20 ft of any window, door or air intake.
- 02A generator connected to house wiring without a transfer switch can backfeed and electrocute anyone working on the line. A proper interlock or transfer switch is mandatory.
- 03Never refuel a hot or running engine. Store fuel in approved containers away from the generator and any ignition source.
- 04Exhaust surfaces exceed 400 °F. Keep the enclosure clear of anything combustible, including dry grass.
- 05Bond and earth the generator frame per local code.
Procedure
0/7 completeSize against the charger, not the house
In a battery-based system the generator's job is to run the inverter/charger flat out and recharge the bank fast. Take the charger's maximum AC input in amps, multiply by voltage, and add any loads that will run simultaneously. Then add 25%. Oversizing wastes fuel and glazes cylinders; undersizing means the charger throttles and you run for hours.
Field tip · Running a generator at 20% load for long periods causes wet-stacking in diesels. Load it properly and run it for less time.
Choose the fuel
Petrol is cheapest to buy and worst to store — it degrades within months. Propane stores indefinitely, burns clean and starts well in cold weather, at a small power penalty. Diesel gives the best fuel economy and longest engine life but needs load. On a remote property, propane usually wins on total practicality.
Site and build the enclosure
At least 20 ft from any occupied structure, downwind of prevailing breezes, on a level concrete pad. Build a sound-damped, well-ventilated enclosure with generous intake and exhaust openings and a baffle-lined path for noise. Never restrict cooling airflow to make it quieter.
Hazard · Extend exhaust away from the enclosure and never toward the house. CO is heavier-feeling than you expect in still air and pools in low ground.
Install the transfer switch
Wire the generator through a transfer switch or a mechanical interlock so that generator and any other source can never be connected simultaneously. In an inverter-based system the AC input of the inverter/charger usually is the transfer switch — verify its internal transfer rating and configuration before relying on it.
Hazard · Backfeeding through a standard outlet — a suicide cord — is illegal and lethal. Never do it.
Set up auto-start
Connect the two-wire start terminals to the inverter's generator control relay. Configure start triggers: low state of charge (say 30%), low DC voltage sustained for several minutes, or high load. Set a minimum run time so the generator never short-cycles, and a quiet-hours window so it never fires at 2 a.m.
Field tip · Set the stop trigger by absorption-time completion rather than a voltage threshold; otherwise the generator stops before the bank is actually full.
Commission and load-test
Run the generator with the charger at full input and measure AC voltage and frequency under load. Verify the charger accepts the power and does not reject it as unstable. Check the transfer sequence works from both directions. Time a full recharge from 30% and record the fuel used — that is your real cost per kWh.
Build the service regime
Fit an hour meter and start a log. Oil and filter at 100 hours or annually, whichever comes first. Exercise the generator under load for 30 minutes monthly even if unused. Keep the start battery on a maintainer. Stock two full service kits on site — a generator you cannot service is a generator you cannot run.
Maintenance schedule
Fault finding
Charger rejects generator power
Likely causeUnstable frequency or dirty waveform
CorrectionWiden the charger's AC input acceptance window, or fit an inverter-type generator. Cheap open-frame sets often cannot hold frequency.
Cranks but will not start
Likely causeStale fuel or a flat start battery
CorrectionDrain and refill with fresh fuel; keep the battery on a maintainer. Both are prevented by the monthly exercise run.
Black smoke and oily exhaust (diesel)
Likely causeWet-stacking from chronic light loading
CorrectionRun at 60 – 80% load for an hour to burn it clear, then resize the run strategy.
Auto-start fires constantly
Likely causeTrigger threshold set too high, or an undersized battery bank
CorrectionLower the start SOC threshold and lengthen minimum run time; if it persists, the bank is too small for the loads.